beautypg.com

Project planning – KROHNE H250 M40 Safety V2 EN User Manual

Page 8

background image

5

PROJECT PLANNING

8

H250 M40

www.krohne.com

06/2013 - 4000904202 MA H250 M40 SIL R02 en

Project planning

5.1 Applicable device documentation

5.2 Project planning, behaviour during operation and malfunction

• The stress levels shall be average for an industrial outdoor environment and shall be similar

to exida Profile 2 or Profile 4 with temperature limits within the manufacture’s rating. Other
environmental characteristics are assumed to be within the manufacturer’s ratings.

• Under normal conditions the maximum operating time will be 10 years.
• Requirements made in the operating manual have to be kept.
• Repair and inspection intervals have to be based on the safety calculations.
• Follow the repair instructions of the manufacturer in the printed manual.
• Modifications made without specific authorisation of the manufacturer are strictly prohibited.
• Follow the installation and operating instructions.
• The application program in the safety logic solver is configured to detect under-range and

over-range failures and does not automatically trip on these failures; therefore these failures
have been classified as dangerous detected failures. The failure rates of the safety logic
solver are not included in the listed failures rates.

• The parameters given by the FMEDA are considered as planning support. The end user is

responsible for the overall functional safety of the application.

• For help to find the correct order text see annex 1.

[D1]

TD H250/M40-Rxx-en
Technical datasheet H250/M40 – Variable area flowmeter

[D2]

MA H250/M40-Rxx-en
Handbook including installation and operating instructions

[D3]

exida FMEDA report: KROHNE 10/10020361 R010 Version 2

MA_H250_M40_SIL2_R02_en_904202_PRT.book Page 8 Wednesday, June 26, 2013 9:04 AM