beautypg.com

Device description, 4 equipment category, 5 protection types – KROHNE ESK4 Ex II2G Ex iEN User Manual

Page 5: 6 ambient temperature / temperature classes

background image

DEVICE DESCRIPTION

2

5

ESK4... ...

www.krohne.com

05/2014 - 4001078702 MA ESK4 Ex II2G AD R02-en

2.4 Equipment category

The electronic signal outputs are designed in category II 2 G or EPL Gb according to EN 60079-0
and EN 60079-11 for use in zone 1.

2.5 Protection types

The electronic signal output is designed with protection type intrinsic safety, protection level "ia"
acc. to EN 60079-11.

The marking acc. to ATEX is: II 2G Ex ia IIC T6 Gb

II 2G Ex ia IIC T6 Gb

II 2G Ex ia IIC T6 Gb

II 2G Ex ia IIC T6 Gb

2.6 Ambient temperature / temperature classes

Depending on the version and the temperature class, the electronic signal outputs are approved
for the following ambient temperatures.

ESK4... permissible ambient temperatures

The marking contains the following information:

The marking contains the following information:

The marking contains the following information:

The marking contains the following information:

II

IIII

II

Explosion protection, group II

2222

Equipment category 2

G

G

G

G

Gas explosion protection

Ex ia

Ex ia

Ex ia

Ex ia

Intrinsically safe, level of protection "ia"

IIC

IIC

IIC

IIC

Suitable for gas groups IIC, IIB and IIA

T6

T6

T6

T6

Suitable for temperature classes T6...T1

Gb

Gb

Gb

Gb

EPL, suitable for zone 1

Type
Signal Output

Temperature class

Ambient temperature in

[°C]

[°F]

ESK4 ...

ESK4-I/O

T6

-40...+60

-40...+140

T5

-40...+75

-40...+167

T4...T1

-40...+85

-40...+185

ESK4-FF

ESK4-PA

T6

-40...+55

-40...+131

T5

-40...+70

-40...+158

T4...T1

-40...+85

-40...+185

AD_ESK4_II2G_R02_en_4001078702_PRT.book Page 5 Wednesday, June 25, 2014 7:19 AM