3.2 A

PPLICATION

Model FP-524C MicroSafe™ sensors are designed to detect and monitor combustible gas in ambient air in the range of

0-100% LEL. Minimum sensitivity and scale resolution is 1%. Operating temperature range is -40° F. to +175° F. While

the sensor is capable of operating outside these temperatures, performance specifications are verified within the limit.

3.2.1 Sensor Placement/Mounting

Sensor location should be reviewed by facility engineering and safety personnel. Area leak sources and perimeter mounting

are typically used to determine number and location of sensors. The sensors are generally located 4-6 feet above grade.

3.2.2 Response to Different Gases

An attractive feature of the catalytic detector elements is their almost universal response to lower explosive limits of

virtually any combustible gas. Most detectable gases produce a similar output, however the signal amplitudes differ.

The table in section 3.7 lists theoretical factors (K factors) for different gases which are a measure of their signal

amplitude as compared to methane which has a K factor of 1.00. Since these factors are theoretical, they will only

give a guide to the response expected from other gases. The Model FP-524C sensor can be conf igured to detect any

of the listed gases. The gas selected for detection is referred to as the target gas. The sensor can also be conf igured

to allow the user to calibrate with a listed gas other than the target gas. This selection is referred to as the calibra-

tion gas. Unless otherwise specif ied, Model FP-524C sensors are conf igured to detect methane and are calibrated

with methane to a scale of 0-100% LEL. Refer to section 3.7 for details.

3.3 S

PECIFICATIONS

Method of Detection

Catalytic detector diffusion/adsorption

Measurment Range

0-100% (lower explosive limit) LEL

Accuracy/Repeatability

± 3% LEL in 0-50% LEL Range

± 5% LEL in 51-100% LEL Range

Response/Clearing Time

T50 <10 seconds; T90 <30 seconds

Zero Drift

< 5% per year

Operating Temperature Range

-40° to +175° F; -40° to +75°C

Operating Humidity Range

0-99% non-condensing

Output

Linear 4-20 mA DC

Input Voltage

12-28 VDC

Power Consumption

1.9 watts @ 24V

Electrical Classification

Explosion Proof; Class I; Div. 1; Groups B, C, D

Safety Approvals

CSA/NRTL (US OSHA Certified)

Sensor Warranty

2 year conditional

3.4 O

PERATING

S

OFTWARE

Operating software is menu listed with operator interface via the two magnetic program switches located under the

face plate (reference f igure 6). The two switches are referred to as “PGM 1” and “PGM 2”. The menu list consists of

3 items which include sub-menus as indicated below. (Note: see the last page of this manual for a complete software

f low chart.)

01.

Normal Operation

Model FP-524C Combustible Gas Sensor PG.6