Detcon FP-700 SIL 2 Safety Manual User Manual
Page 6
![background image](/manuals/366692/6/background.png)
17
OPERATING, ENVIRONMENTAL, AND PERFORMANCE SPECIFICATIONS
The Safety-Certified FP-700 product versions fully comply with, and must be operated in accordance with the functional,
environmental, and performance specifications provided in the FP-700 instruction manual. A 24 hour mean time to repair
should be assumed for safety availability calculations. All FP-700 diagnostics have a maximum 2 hour test interval.
18
SPARE PARTS
Refer to “Spare Parts” in the FP-700 instruction manual. Safety Certification is based on having a sufficient number of
spares to achieve a 24 hour mean time to repair.
19
CERTIFICATION AND FAILURE RATE DATA
All Safety-Certified FP-700 models are certified compliant to:
IEC61508:2010
SIL 2 Certified
PFDavg @ 1 year is 24.7% of the SIL2 range.
Safe Failure Fraction (SFF):
90.1%
Safety Accuracy:
+/-20% FS Range
Safety Response Time for % LEL Methane:
< 60 seconds to T90
Product Life:
10 years (Intelligent Transmitter Module)
3 years+ (Catalytic Bead Cell)
20
CERTIFICATIONS
cCSAus, ATEX, CE Marking (Refer to the Model FP-700 Instruction Manual for details).
FMEDA Report available.
For complete information regarding performance, installation, operation, maintenance and specifications of Model FP-
700, refer to the instruction manual Document #3168.
21
REVISION LOG
Revision
Date
Changes made
Approval
1.0
10/31/13
Initial Release
RJM
2.0
12/09/13
Added product life for cat bead cell
RJM