17

OPERATING, ENVIRONMENTAL, AND PERFORMANCE SPECIFICATIONS

The Safety-Certified FP-700 product versions fully comply with, and must be operated in accordance with the functional,
environmental, and performance specifications provided in the FP-700 instruction manual. A 24 hour mean time to repair
should be assumed for safety availability calculations. All FP-700 diagnostics have a maximum 2 hour test interval.

18

SPARE PARTS

Refer to “Spare Parts” in the FP-700 instruction manual. Safety Certification is based on having a sufficient number of
spares to achieve a 24 hour mean time to repair.

19

CERTIFICATION AND FAILURE RATE DATA

All Safety-Certified FP-700 models are certified compliant to:

IEC61508:2010
SIL 2 Certified
PFDavg @ 1 year is 24.7% of the SIL2 range.
Safe Failure Fraction (SFF):

90.1%

Safety Accuracy:

+/-20% FS Range

Safety Response Time for % LEL Methane:

< 60 seconds to T90

Product Life:

10 years (Intelligent Transmitter Module)
3 years+ (Catalytic Bead Cell)

20

CERTIFICATIONS

cCSAus, ATEX, CE Marking (Refer to the Model FP-700 Instruction Manual for details).

FMEDA Report available.

For complete information regarding performance, installation, operation, maintenance and specifications of Model FP-
700, refer to the instruction manual Document #3168.

21

REVISION LOG

Revision

Date

Changes made

Approval

1.0

10/31/13

Initial Release

RJM

2.0

12/09/13

Added product life for cat bead cell

RJM