beautypg.com

Operation & adjustment instructions 17, Setup modes – Allstar Products Group MH5011S User Manual

Page 17

background image

OPERATION & ADJUSTMENT INSTRUCTIONS

17

Setup Modes

Various operating characteristics can be modified via the setup
modes. The operator is moved to the close limit position and
the on-board dip switches (see Figure 15) are

TEMPORARILY

set according to the table at right to enter a Setup Mode. The on
board OPEN and STOP buttons are used to modify the
characteristic. Once set, the values are stored in non-volatile
memory.
These values are set to factory defaults that should be
satisfactory for many applications. All values as described here
can be reset to the factory defaults as follows:

Remove 24 VAC power from the control board.

Press and hold the on-board stop button.

Re-apply 24 VAC while holding the on-board stop button.

After completing the procedure to modify the operating

characteristic the switches must be returned to the originally set
Operating Mode setting (see section previous).

Delay on Reverse Setup

To help prevent stress on the door components, this feature

allows for a delay time between the door stopping and reversing
when a command to reverse is received as the door is closing.
The factory default time is 0.75 seconds; the minimum time is
0.4 seconds; the maximum time is 2 seconds.

After moving the door to the close position and temporarily

setting the switches to the appropriate settings in the table,
pressing STOP will reset the time to the minimum setting.

Every time OPEN is pressed, 200 mS is added to the time (up to

the maximum).

Changing the dip-switch setting to any other setting will save

the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).

Close Limit Delay Setup

To provide for irregularities in the floor, this feature allows for

the door to continue to travel down after the Reverse Cutout
Limit is activated. The factory default time is 0.32 seconds; the
minimum time is 0.12 seconds; the maximum time is 0.66
seconds.

After moving the door to the close position and temporarily

setting the switches to the appropriate settings in the table,
pressing STOP will reset the time to the minimum setting.

Every time OPEN is pressed, 0.02 seconds are added to the time

(up to the maximum).

Changing the dip-switch setting to any other setting will save

the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).

Mid-Stop Limit Setup

This features provides a timing function to stop a door as it is

traveling open at a Mid Stop position instead of the full open
position. The door can then be moved to the full open position
if desired by pressing the Open button. A single button input
when the door is at the mid stop position will cause the door to
begin moving in the close direction. The factory default is not
set; the minimum run time to mid-stop limit is 6 seconds.

After moving the door to the close position and temporarily

setting the switches to the appropriate settings in the table,
pressing STOP will remove the mid-stop limit setting.

Pressing OPEN will start the door open. When the door reaches

the desired mid-stop position, press STOP.

Changing the dip-switch setting to any other setting will save

the mid-stop limit position. Return the dip switches to the
originally set Operating Mode setting (see section previous).

Note: The door must move a sufficient distance to fully

disengage the Reverse Cutout Limit nut from the Reverse Cutout
Limit switch to set the mid-stop limit.

Auto Close Timer Setup

This feature allows for a modification of the amount of time

between the door reaching either the Mid Stop or the Full Open
position and automatically starting in the close direction. The
Auto Close feature is only active when the operator is set to the
T or TS Operating Mode (see section previous). The factory
default is 30 seconds; the minimum time is 5 seconds; the
maximum time is 5 minutes.

After moving the door to the close position and temporarily

setting the switches to the appropriate settings in the table,
pressing STOP will clear and turn off the auto close timer.

Every time OPEN is pressed, 5 seconds is added to the time.
Changing the dip-switch settings to any other settings will save

the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).

Maximum Run Time Setup

This feature provides for a maximum amount of time the motor

will be energized after an input is recognized. The factory
default time is 30 seconds; the maximum time is 60 seconds.

After moving the door to the close position and temporarily

setting the switches to the appropriate settings in the table,
pressing STOP will reset the time to the factory default setting.

Pressing OPEN will start the door open. The run time will be

recorded when the door reaches the open limit. To prevent
nuisance problems, 0.75 seconds are added to this time. Pressing
stop before the door reaches the open limit will stop the door
and reset the time to the factory default.

Changing the dip-switch setting to any other setting will save

the new time

.

Return the dip switches to the originally set

Operating Mode setting (see section previous).


Setup Mode

Switch 1 Switch 2 Switch 3 Switch 4

Delay on Reverse

ON

ON

ON

ON

Mid-Stop Limit

ON

OFF

ON

ON

Auto Close Timer

OFF

OFF

ON

ON

Maximum Run Time

OFF

ON

OFF

ON

Close Limit Delay

OFF

ON

ON

ON

SETUP MODES

This manual is related to the following products: