beautypg.com

Eletrical requirements – RIKON Power Tools 30-120 User Manual

Page 14

background image

Eletrical Requirements

In the event of a malfunction or breakdown, grounding provides a path of least resistance for electric

current to reduce the risk of electric shock. This tool is equipped with an electric cord having an

equipment-grounding conductor and a grounding plug. The plug must be plugged into a matching

outlet that is properly installed and grounded in accordance with all local codes and ordinances.

Do not modify the plug provided. If it will not fit the outlet, have the proper outlet installed by a

qualified electrician.

Improper connection of the equipment-grounding conductor can result in a risk of electric shock. The

conductor, with insulation having an outer surface that is green with or without yellow stripes, is the

equipment-grounding conductor. If repair or replacement of the electric cord or plug is necessary, do

not connect the equipment-grounding conductor to a live terminal.

Check with a qualified electrician or service personnel if the grounding instructions are not completely

understood, or if in doubt as to whether the tool is properly grounded.

Use only three wire extension cords that have three-prong grounding plugs and three-pole receptacles

that accept the tool’s plug.*

Repair or replace a damaged or worn cord immediately.

This tool is intended for use on a circuit that has an outlet that looks the one illustrated in Figure

A below. The tool has a grounding plug that looks like the grounding plug as illustrated in Figure A

below. A temporary adapter, which locks like the adapter as illustrated in Figure B below, may be

used to connect this plug to a two-pole receptacle, as shown in Figure B if a properly grounded outlet

is not available.** The temporary adapter should only be used until a properly grounded outlet can

be installed by a qualified electrician. The green colored rigid ear or tab, extending from the adapter,

must be connected to a permanent ground such as a properly grounded outlet box.

* Canadian electrical codes require extension cords to be certified SJT type or better.

** Use of an adapter in Canada is not acceptable.

14