... NOTE
...
Several audible changes may be heard during the recovery and recycling process.
Refrigerant flow through check valves causes a "sizzle-type" sound.
These changing "noises" are normal and nothing to be concerned about.
5.
Press top (ON) of rocker switch marked RECOVER/RECYCLE.
The TC2670 will recover and recycle refrigerant from the A/C System, and then automatically cycle
off when a vacuum is sensed. This vacuum level can be seen on the Low Side Gauge.
!
! DO NOT TURN THE TC2670 OFF OR DISCONNECT HOSES !
!
A small quantity of Liquid refrigerant will probably still remain in the A/C System. This can be
detected by observing an increasing pressure reading on the Low Side Gauge.
As pressure rises to a preset level, the TC2670 will automatically cycle on to continue recovering
refrigerant. Allow this automatic On/Off sequence to repeat until the vacuum level remains constant
for at least 2 minutes.
6.
Close Red and Blue Hose Valves.
7.
Close High and Low Gauge Valves.
8.
Press bottom (OFF) of rocker switch marked RECOVER/RECYCLE.
8.
Press bottom (OFF) of rocker switch marked R12 POWER.
PURGE REQUIRED OR CYLINDER FULL LIGHT:
This Light will illuminate if either...
1)
Pressure on the Purge Gauge approaches 250 psig: Go to Page 9
OR
2)
The Charging Cylinder has filled to capacity: Go to Page 12