8

... NOTE

...

Several audible changes may be heard during the recovery and recycling process.

Refrigerant flow through check valves causes a "sizzle-type" sound.

These changing "noises" are normal and nothing to be concerned about.

5.

Press top (ON) of rocker switch marked RECOVER/RECYCLE.

The TC2670 will recover and recycle refrigerant from the A/C System, and then automatically cycle
off when a vacuum is sensed. This vacuum level can be seen on the Low Side Gauge.

!

! DO NOT TURN THE TC2670 OFF OR DISCONNECT HOSES !

!

A small quantity of Liquid refrigerant will probably still remain in the A/C System. This can be
detected by observing an increasing pressure reading on the Low Side Gauge.

As pressure rises to a preset level, the TC2670 will automatically cycle on to continue recovering
refrigerant. Allow this automatic On/Off sequence to repeat until the vacuum level remains constant
for at least 2 minutes.

6.

Close Red and Blue Hose Valves.

7.

Close High and Low Gauge Valves.

8.

Press bottom (OFF) of rocker switch marked RECOVER/RECYCLE.

8.

Press bottom (OFF) of rocker switch marked R12 POWER.

PURGE REQUIRED OR CYLINDER FULL LIGHT:

This Light will illuminate if either...

1)

Pressure on the Purge Gauge approaches 250 psig: Go to Page 9

OR

2)

The Charging Cylinder has filled to capacity: Go to Page 12