EVACUATE TX200
The TX200 is designed to recover different refrigerants. A small amount of refrigerant always remains
in the internal components of the TX200 after each recovery procedure. This residual refrigerant
needs to be evacuated from the TX200 prior to recovering a different refrigerant. The following
procedure will remove all residual refrigerant.
Connect TX200 as shown.
Turn TX200 Valve to EVACUATE.
Open low side valve on Gauge Manifold.
Press top of ON/OFF Switch.
Open all three hose valves.
Open liquid valve on Cylinder.
All refrigerant will be evacuated from the TX200 and stored in the Cylinder. The COMPRESSOR ON
Light will go off.
Press and hold the DEEP VACUUM Switch for 30 seconds.
Press bottom of the ON/OFF Switch.
Close liquid valve on Cylinder.
Close all hose valves.
Close low side valve on Gauge Manifold.
Turn TX200 Valve to OFF.