Recover – MAHLE RTI TX200 User Manual
Page 5
Page 4
RECOVER
(Continued)
Open all hose valves and the liquid valve on the cylinder.
Turn the TX200 valve to RECOVER.
Press the top of the ON/OFF Switch. The switch will illuminate to indicate that power is on.
The COMPRESSOR ON Light will illuminate and the TX200 will begin recovering refrigerant.
The CYLINDER FULL Light will illuminate if the cylinder fills to capacity.
The TX200 will recover refrigerant until a vacuum is indicated on the low side gauge.
The compressor will turn off and the COMPRESSOR-ON Light will turn off.
DO NOT TURN THE TX200 OFF OR DISCONNECT HOSES.
A small quantity of liquid refrigerant will probably remain in the cooling system. This liquid will vaporize
and increase the pressure in the cooling system as components again warm to ambient temperature.
The TX200 will again start to recover refrigerant if pressure increases to a preset level. The
compressor will turn on and the COMPRESSOR-ON Light will illuminate.
Allow this sequence to repeat until the COMPRESSOR-ON light stays off for at least two minutes.
The DEEP VACUUM Switch can be pressed to draw a deeper vacuum if desired.
Push bottom of the ON/OFF Switch to turn off the TX200.
Turn the TX200 valve to OFF.
Close all hose and cylinder valves and disconnect the TX200 from the cooling system.