Yokogawa 212 Heat Calculator User Manual
Page 23

Parameter
Value
Description
If 4-20mA Output is installed
8. 4-20mA
Flow
Pwr
∆
t°
Ft°
Rt°
Defines the parameter to be output as a
4-20mA signal.
9.
4mA
xxxx.xxx
Flowrate or temperature which
corresponds to 4mA.
10.
20mA
xxxx.xxx
Flowrate or temperature which
corresponds to 20mA.
12.
PULSE
Ener
Volu
Defines whether the pulse output is for
the energy or volume total.
13.
PULSE
xxx.x kWh
Defines how often a pulse is output
(maximum frequency = 49Hz).
14.
COMMS
NONE
M-BUS
RS485
No Communications.
Meter-bus (see Section 4).
Modbus RTU.
15.
BAUD
xxxx
Communications baud rate between 300
and 9600.
16.
PARITY
Even/Odd/None Communications parity.
17. BUS
xx
ADDR
Bus address for the communications link.
Operation 21