Yokogawa 202 Field Mounting Rate Totalizer User Manual
Page 27

Versions
23
Specification for Alarm Outputs
Maximum Current (sink):
200mA.
Maximum Voltage:
30Vdc.
Saturation Voltage:
0.8Vdc across outputs when in the "on" state.
Isolation:
Both outputs are separately isolated.
Pulse Frequency:
500Hz maximum.
Pulse Duration:
1ms if CAL0 = 2 (unscaled pulse output).
If CAL0 = 1 (scaled pulse output) the duration of
the pulse automatically adjusts to the output
frequency:
a.
1ms if output > 50Hz.
b. 10ms if output = 5...50Hz.
c.
100ms if output < 5Hz.