4.1 PROGRAM STEPS
Step
Comment
CAL 0
Pulse Output (applies to DC Power/Alarm version only).
0 = No pulse output, low and high alarms.
1 = Scaled pulse output and low alarm.
2 = Unscaled pulse output and low alarm.
CAL 1
Scaling Factor - whole numbers.
CAL 2
Scaling Factor - digits after the decimal point.
The scaling factor is the pulses per unit of measure (eg.
pulses/litre, pulses/gallon, etc). The scaling factor can be
programmed in the range of 0.000001 - 999,999.
See Section 3.4.
CAL 3
Cutoff Frequency.
This determines the cutoff frequency in the range of 0.01 -
0.99Hz. The default setting is 0.25HZ.
Note that care must be taken when programming this value
because a low value may cause a slow update time.
CAL 4
Decimal Point for Rate Display.
The flow rate can be displayed with 0, 1, 2 or 3 decimal point
places.
CAL 5
Timebase for Rate.
The rate can be displayed in units per second, minute, hour or
day.
0 = second
1 = minute
2 = hour
3 = day