half) it is recommended to allow the link to “float” using “S” hooks, straps or other

attachments.

ELECTRICAL CHARACTERISTICS

The ETL69C-40 is rated 24 VDC, 200mA. It contains a bridge wire initiated

pyrotechnic heating element. The 14u bridge wire has a nominal resistance of 10 to

30 Ohms. The bridge wire serves as the ignition source for the chemical heater core.

The design of the bridge wire has been optimized, requiring minimal energy to

function while remaining safe to handle, transport and install.

Care should be exercised in handling and installing the ETL69C-40 with particular

attention to the following electrical characteristics: Avoid proximity to electrostatic

discharge or heavy induction fields. Keep the lead wires twisted or otherwise

shunted unless performing resistance checks or until making final connection. Keep

the ETL69C-40 inside the packaging box when not in use, or wrap it in aluminum

foil to protect it from unwanted accidental exposure to stray current such as radio

transmission fields; electric motor induction fields; electrical coils, and static

discharge.

The ETL69C-40 Link integrates a relay that isolates the bridge wire in the thermal

element. When an alarm system “end of the line” device is wired to the link input

and the link and is terminated to a Listed UL 864 Fire Alarm Control unit

compatible with this device the wiring should be supervised. When wired, the

listed control unit continuously monitors the link circuit, per the wiring diagram.

Even minimal continuous input current through the bridge wire will cause long term

“baking” of the internal chemical core, and allow ingress for an undesired current at

levels sufficient to cause unwanted actuation of the device.