Troubleshooting Tips

Compressor does not start

Problem: Compressor circuit breaker has tripped.
Solution: Depress the circuit breaker switch.
Problem: HIGH PRESSURE light is on.
Solution: The high side pressure switch has tripped; verify the tank and

hose ball valves are open. Check tank and verify it is not full.

Problem: COMPRESSOR switch is not on.
Solution: Press the COMPRESSOR switch to ON.

Compressor runs but does not move refrigerant

Problem: The ball valves on the hoses are not open.
Solution: Open the ball valves.

Problem: The tank valves are not open.
Solution: Open the valves.

During recovery, unit shuts off on high pressure

Problem: The refillable tank valves are not open.
Solution: Open the tank valves.

Problem: Valves on hoses are shut.
Solution: Open valves.

Unit will not pull down to appropriate vacuum level

Problem: There is a leak in the A/C system.
Solution: Fix the leak.

Problem: Trapped pockets of refrigerant.
Solution: Allow system to stabilize then heat with a heat gun.