Troubleshooting guide – Robinair Model 15600 User Manual
Page 7

6
b) Another method of dealing with heavily contaminated oil is to force
the oil from the pump reservoir. To do this, allow the pump to run
until it is warmed up. While the pump is still running, remove the oil
drain cap. Slightly restrict the exhaust. This will back-pressure the oil
reservoir and force the oil from it, carrying more contaminants. When
the oil ceases to flow, turn off the pump.
Repeat this procedure as required until the contamination is removed.
Replace the OIL DRAIN cap, and refill the reservoir to the correct level
with fresh pump oil (see Step 4).
Clean the pump using only soap and water. Do not use commercial
cleaners containing degreasing agents that can damage polycarbonates.
The pump handle and base are made of Lexan
®
, one of the toughest
polycarbonate plastics available, but it is sensitive to degreasing agents.
*Lexan is a registered trademark of General Electric.
Troubleshooting Guide
This Robinair pump has been designed for dependable use and long life.
If something should go wrong, however, the following guide will help
you get the pump back into service as quickly as possible.
If disassembly of the pump is required, please check your warranty. The
warranty may be voided by misuse or customer tampering that results in
the pump being inoperable.
Check line voltage. Robinair pumps are designed to start at +10% line
voltage (loaded) at 32
o
F. At extremes, however, switching between the
start and run windings may occur.
1. Verify the oil is not a residual accumulation from spillage, etc.
2. If leakage exists, the module cover gasket or the shaft seal may need
replacing. Follow the instructions supplied with Seal Replacement Kit
No. 15367. If leakage exists in the area of the oil drain plug, you may
need to reseal the plug using a commercial pipe thread sealer.
1. Verify the Iso-Valve™ on the pump is in the OPEN position.
2. Verify the vacuum gauge and all connections are in good conditon and
leak-free. Confirm leakage by monitoring the vacuum with a thermistor
gauge while applying vacuum pump oil at connections or suspected leak
points. Vacuum will improve briefly while the oil is sealing the leak.
Cleaning
the Pump
Failure
To Start
Oil
Leakage
Failure
To Pull
A Good
Vacuum