Troubleshooting guide – Ransburg RCS-100FP Fluid Pump Kit 70945 User Manual
Page 17

LN-9227-00
13
13
13
13
13
Fluid Pump Motor Speed Control Station - Maintenance
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE
Figure 5: Troubleshooting Guide
Figure 5: Troubleshooting Guide
Figure 5: Troubleshooting Guide
Figure 5: Troubleshooting Guide
Figure 5: Troubleshooting Guide
General Problem
General Problem
General Problem
General Problem
General Problem
Cause
Cause
Cause
Cause
Cause
Solution
Solution
Solution
Solution
Solution
Motor Will Not Start
Controller Line Fuse
Blows When AC Line
Power is Applied to the
Controller
1. AC line open
2. Operator controls inop-
erative or connected
incorrectly
3. Relay 1RE bad
4. Line voltage selection
jumper J1 in wrong po-
sition
5. Controller not enabled
6. Controller not adjusted
correctly
7. Open shunt field wind-
ing or wiring to the mo-
tor shunt field, causing
loss of torque
8. Motor failure
9. Control board failure
1. Wiring faulty or incor-
rect
2. Circuit, component, or
wiring grounded
3. Motor shunt field
shorted or grounded
4. Control board failure
1. - Be sure rated AC line voltage is ap-
plied to controller.
- Measure for 115 VAC between TB1-
L2 and 1RE-8.
2. Hold HV control ON, measure HV inter-
lock input voltage.
115 VAC - TB3-1 to TB3-3 -or-
24 VAC - TB3-2 to TB3-3 -or-
24 VDC - TB3-2 to TB3-3
3. Be sure HV control ON signal is present
(above). Measure for 115 VAC between
TB1-L1 and TB1-L2. If not, replace 1RE.
4. Be sure J1 is in the 115 VAC position.
5. Be sure that TB2-8 is jumpered to TB2-9.
6. Turn the ACCEL and CUR LMT potenti-
ometers fully clockwise (100%).
7. Check the motor shunt field and associ-
ated circuitry for a loose or broken wire.
8. Repair or replace motor.
9. Repair or replace the controller.
1. Check all external wiring terminating in
the controller.
2. Remove ground fault.
3. Repair or replace motor.
4. Repair or replace controller.