Finish Thompson Little Cooler User Manual
Page 10

10
PROBLEM: Unit will not turn on
POSSIBLE CAUSES:
Improper electrical hook-up. Verify proper installation of electrical supply.
No power to the unit. Check main circuit breaker and/or electrical supply to the unit.
PROBLEM: Fan runs, but not the pump.
POSSIBLE CAUSES:
NOTE: If the liquid temperature from the radiator exceeds 150
F, a safety temperature switch
will shut down the pump of the Little Cooler. The fan will continue to run to assist cooling the
liquid. Once the liquid cools to below 100
F, the pump will turn back on.
Coolant level is low in the reservoir. Top off to proper level.
Ambient air temperature too high. Verify proper ventilation of the unit.
Heat exchange system dirty. Clean the finned surfaces of the radiator.
Pump components melted from being run dry. Replace pump assembly.
Pump’s motor is defective. Replace motor.
PROBLEM: Distillation unit shuts down, but the Little Cooler is still running.
POSSIBLE CAUSES:
Improper installation of Little Cooler. Verify that the distance from distillation system is
within allowable limits and the plumbing to the Little Cooler is correct.
Coolant level is low in the reservoir. Top off to proper level.
Leak(s) in piping. Verify tight plumbing connections.
Build-up of debris in Y-strainer. Clean the screen in the Y-strainer.
Defective or dirty flow switch in distillation unit. Service according to the distillation unit
owner’s manual.
PROBLEM: Vapors escaping from the discharge hose of the distillation system.
POSSIBLE CAUSES:
Solvent’s boiling point too low. Do not process solvents with boiling points below 150F.
Flow switch in distillation system defective and improper coolant flow. Service the flow
switch and determine cause of low coolant flow.
Little Cooler turned off prematurely. Allow the Little Cooler to run for an additional hour
after the distillation unit is shut down.
Vapor condenser in distillation unit plugged (scale/mineral deposits, debris, etc.) Clean or
replace the distillation unit’s condenser.
COMMON SPARE PARTS:
PART # DESCRIPTION
PART
# DESCRIPTION
A101299
Pump Assembly
J101235
Safety switch (TAS1)
J101444 Pump
motor
J101210
Radiator
J101212
Fan blades
M101103
Reservoir tank
J101558
Fan motor
J101431
Fill hole cap
J103909
½” H x ½” H hose barb fitting