beautypg.com

Agilent Technologies 6012B EN User Manual

Page 29

background image

Operating Instructions 29

Table 3-2. Maximum Wire Lengths To Limit Voltage Drops

Wire Size

Resistivity

Maximum Length In Meters (Feet)To

Limit Voltage Drop To 0.5V Or Less

AWG

Cross-section (mm

2

)

/kft

/km

5 A

10A

17 A

30A

50A

120A

22

16.15

(6.19)

*

*

*

*

*

0,5

40.1

2.5

*

*

*

*

*

20

10.16

(9.8)

*

*

*

*

*

0,75

26.7

3.7

1.8

*

*

*

*

18

6.388

(15.6)

(7.8)

*

*

*

*

1

20,0

5.0

2.5

*

*

*

*

16

4.018

(24.8)

(12.4)

(7.3)

*

*

*

1,5

13.7

7.3

3.64

*

*

*

*

14

2.526

(40)

(19.7)

(11.6)

(6.6)

*

*

2,5

8.21

12.2

6.1

3.5

*

*

*

12

1.589

(62.9)

13.46)

(18.5)

(10.49)

*

*

4

5.09

19.6

9.8

5.7

3.27

*

*

10

.9994

(100)

(50)

(29.4)

(16.68)

(10.01)

*

6

3.39

29.5

14,7

8.6

5.9

*

*

8

0.6285

(160)

(79.5)

(46.7)

(26.52)

(15.91)

*

10

1.95

51,2

25,6

15

8.55

5.13

*

6

0.3953

(252)

(126.5)

(74.4)

(42.16)

(25.3)

*

16

1.24

80.6

40,3

23.7

13.44

8.06

*

4

0.2486

(402)

(201)

(118)

(67.04)

(40.23)

(16.76)

25

0.795

125.7

62.8

37

20.96

12.58

5.24

2

0.1564

(639)

(319)

(188)

(106.5)

(63.94)

(26.64)

35

0.565

176.9

88.5

52

29.5

17.7

7.37

50

0.393

254.4

127

74.8

42.4

25.45

10.6

0

0.09832

(1017)

(508)

(299)

(169.5)

(101.7)

(42.38)

* Wire not rated for power supply maximum current rating.

Table 3-3. Stranded Copper Wire Ampacity

Wire Size

AWG

Cross Section (mm

2

)

Ampacity

NOTES:

22

5.0

20

8.33

0.75

10

1

13.5

18

15.4

1.5

16

16

19.4

2.5

25

14

31.2

4

32

12

40

6

40

10

55

10

63

8

75

6

100

4

135

2

180

0

245

1. Ratings for AWG-sized wires are derived from MIL-W-
5088B. Ratings for metric-sized wires are derived from IEC
Publication 335-1.
2. Ampacity of aluminum wire is approximately 84% of that
listed for copper wire.
3. When two or more wires are bundled together, ampacity for
each wire must be reduced to the following percentages:
2 conductors 94%
3 conductors 89%
4 conductors 83%
5 conductors 76%
4. Maximum temperatures: Ambient, 50

°

C; conductor, 105

°

C

This manual is related to the following products: