VERTICAL VENTING

When vertical single 10-inch (25.4 cm) venting is used (refer to Illus. B below), the ductwork from the dryer to
the outside outlet cannot exceed 40 feet (12.19 meters). This calculation compensates for the use of a maximum
of three (3) elbows including the two (2) elbows creating the 180° (turned downward) outside outlet.

Illus. B

If the length of the duct run or quantity of elbows used exceeds the above noted specifications, the
cross-sectional area of the ductwork must be increased in proportion to the number of elbows or duct run
added.

IMPORTANT: For extended ductwork runs, the cross section area of the duct can only be increased

to an extent. For extended ductwork runs, a professional heating, venting, and air
conditioning (HVAC) firm should be consulted for proper venting information.