Troubleshooting – Poweramp CENTRAPOWER User Manual
Page 19

TROUBLESHOOTING
17
4111-0030 — Nov.2009
Symptom
Possible Cause
Solution
Platform or restraint 
does work. Motor does 
not energize.
Motor overload device 
tripped or fuse blown.
Reset 3phase overload relay (Located next to pump 
station) or replace fuse. Reset 120 volt overload 
relay or replace fuse in the individual control box’s.
NOTE: When replacing fuse(s), the new fuse must
have the same specification as the old fuse.
No voltage at over loads or 
relays
Check voltage at starter or relay coil.
•
If voltage is present and starter or relay does not 
energize, replace starter or relay.
•
If voltage is not present, check all components in 
series with the starter or relay coil. 
Troubleshooting
•
Check all fuses inside the control panel(s). Replace 
any blown fuse(s) with a fuse of equal specification.
•
Make sure the correct voltages are present at the 
proper locations inside the control panel(s).
Before performing the detailed troubleshooting procedures, check the following items first: