2 status messages – Orion Instruments Jupiter 2xx FOUNDATION Fieldbus User Manual
Page 23
57-649 Jupiter Magnetostrictive Transmitter - F
OUNDATION
fieldbus™
23
5.1.2
Status Messages
Display Message
Action
Comment
OK
None
Normal operating mode
Initial
None
Shown at power-up during
self check
Default Cal
Factory set default calibration parameters
Consult Factory
are in use, level reading may be inaccurate
Lo Temp
Present temperature in electronics
Transmitter may need to be moved
compartment is below -40° C
to ensure temperature is within
specification
Hi Temp
Present temperature in electronics
Transmitter may need to be moved
compartment is above +80° C
to ensure temperature is within
specification
Float 2
No level signal detected from float 2
Make sure 2 floats are being used,
Fail
are not damaged, and within
measuring range
Float 1
No level signal detected from float 1
Make sure float is not damaged
Fail
and within measurement range
No Signal
No signal detected from any float
Make sure float is not damaged
and within measurement range
Snsr Brd Fail
No signal from probe, bad board or
Check electrical connections
connection problem
to probe
DfltParm
Internal non-volatile, parameters have
Consult Factory
been defaulted