The following list represents the parameter configuration
required for a Model 705 GWR transmitter intended to
measure overall product level in a SIL 2/3 application.
Please ensure that all Probe-specific parameters are correct
for the GWR probe being used.
PROBE MODEL = As indicated on probe nameplate
PROBE MOUNT = As indicated on probe nameplate
MEASUREMENT TYPE = Level Only
LEVEL UNITS = As indicated on probe nameplate
PROBE LENGTH = As indicated on probe nameplate
LEVEL OFFSET = As required by application
DIELECTRIC = As required by application. (Suggest 1.7–3
for typical hydrocarbon application)
LOOP CONTROL = Level
LOOP CONTROL MODE = Enabled
SET 4mA/SET 20mA = As required by application
DAMPING = As required by application (Default value is 1)
FAULT = As required by application (Default value is
22 mA—do not set to Hold).
BLOCKING DISTANCE = 0 inches
THRESHOLD = Fixed
5.6.3 Write Protection / Locking
Only authorized personnel should be able to change the
transmitter configuration in a device installed in a SIS system.
This requires setting a user password.
The ECLIPSE Model 705 is password protected with a
numerical password between 0 and 255. (Default = 0 means
password is disabled).
The default password must be changed so that password
protection is enabled in a SIS system.
Refer to section 2.6.4 of the Enhanced ECLIPSE Model 705
Installation and Operating Manual 57-600 for additional
information regarding password protection.
Ensure that an exclamation mark (!) appears as the last char-
acter on the first line of the LCD to confirm the present
password has been accepted.
When alterations to the configuration are complete, ensure
the menu has been write-locked with the password to pre-
vent inadvertent changes to the device.
8
57-651 Eclipse
®
SIL Certified Safety Manual for Enhanced Model 705-51AX-XXX