0 troubleshooting guide – Detroit Radiant Products Company DX3 Series User Manual

Page 14

background image

Is the blower

obstructed?

Replace circuit board.

14

Does the igniter warm

up and glow red?

Is the igniter

physically

damaged?

Check voltage at igniter during

ignition sequence (usually 30-

45 seconds after power to the

heater). Is it 120V?

Is the inlet or the outlet of

the unit obstructed (i.e.,

ice, birds nest, dirt, etc.)?

4.0

Troubleshooting Guide

4.0

Troubleshooting Guide

Turn up thermostat

Does the fan

blower turn on?

Is the power at the

heater 120V?

Find the source of the electrical

problem between panel and heater.

No

Yes

DX3

Series

Remove obstruction

and lubricate fan.

No

Yes

Does the switch

light energize?

Yes

Is the light burnt out?

If so, replace.

No

No

Yes

Remove obstruction.

No

No

No

No

Yes

Yes

Replace igniter.

Does valve light

energize?

Yes

Does the burner

ignite at all?

No

The circuit board and/or wiring

harness may be faulty and

needs to be replaced.

No

Yes

Replace faulty light.

Does valve open?

Yes

Yes

Continued on page 16.

No

Test for 120V at valve opening

period (usually 30 to 45 seconds

after power to heater). Is there

120V to valve for 8 seconds?

Replace circuit board and/or wiring harness.

Yes

No

No

Yes