Specifications

Analog Input

Range

Resolution

Accuracy

Input Ohms

DC Voltage

± 200.00 mV

± 2.0000 V
± 20.000 V
± 200.00 V

± 600.0 V

10 µV

100 µV

1 mV

10 mV

100 mV

± 0.01% FS

± 2 counts

1 GΩ
1 GΩ

10 MΩ
10 MΩ
10 MΩ

± 2.0000 mA
± 20.000 mA
± 200.00 mA

0.1 µA

1 µA

10 µA

± 0.01% FS

± 2 counts

100 Ω

10 Ω

1 Ω

DC Current

± 5.000 A

1 mA

± 0.1% FS
± 2 counts

0.01 Ω

Input Resolution
Update Rate, Max
Max applied voltage
Over-current protection

16 bits (65,536 steps)
50/sec at 50 Hz, 60/sec at 60 Hz
600 Vac for 20, 200 & 600 V ranges, 125 Vac other ranges
25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, 1x for 5 A

Analog Output (standard)

Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
Step response time

0-20 mA or 0-10 Vdc (selectable)
10V (0-500Ω load)
2 mA (5 kΩ load)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
50 ms

Dual Relay Output (standard)

Relay Type
Load Rating

Two solid state relays, SPST, normally open, Form A
120 mA at 140 Vac or 180 Vdc

Transducer Excitation Output (standard)

Output Levels
Output Isolation

5V@100 mA, 10V@120 mA, 24V@50 mA (jumper selectable)
50V from signal ground

Serial Data Output (standard)

Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing

RS232 or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater.

Power Input

Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption

85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output

Mechanical

Dimensions
Mounting
Electrical Connections

129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors

Environmental

Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required

0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.