Technical specification – Custom Electronics AOV Multi Zone User Manual
Page 11

5) Technical Specification
Power Supply Unit 5 Amp / 10 Amp
Input Supply
240v AC (+/- 10%) 50/60Hz
Input Fuse
1 - 10 Zone
5Amp, 25mm UK Type quick blow.
11 Zones +
13 Amp, 25mm UK Type quick blow.
Power Supply Unit Outputs
Voltage
Load: 24v DC (+/- 5%)
Battery Charger: 27.6v DC
Load
Zones 1 -5. 1 Amp single output as standard
Battery
Charge:
1
Amp
maximum
Fuses
Input to PCB
Fuse no. FS4.
5 Amp 20mm x 5mm quick blow.
Load Output
Fuse no. FS2.
3 Amp Single output as standard
20mm
x
5mm
quick
blow
Battery
Fuse no. FS1.
3 Amp 20m x 5mm quick blow.
Deep discharge protection is a feature on all models. This will cut off the battery supply to the load at 18v.
Standby Batteries
Capacity
Up
to
17Ah
Types
2 x 12v sealed lead acid batteries from Yuasa or other similar manufacturers.
Max. charge current
1 Amp
Max load output current
5 Amp
Quiescent standby drain
xxmA @ 24v DC
Note: two 12v Batteries are required. It is important that both batteries are the same size and of the same age and condition to
give the maximum performance.
Indicators
Enclosure Front Panel
Green LED lit shows Mains AC supply present.
Amber
LED
lit
shows
common
fault.
PCB
LED2
Green
–
lit
when
LED4
Green
–
lit
when
LED3
Yellow
–
lit
when
LED5
Yellow
–
lit
when
LED6
Yellow
–
lit
when
Fault Monitoring
Main fail
LED2 and lid-card green LED out
Battery not charging
LED4 green stays off
Battery short circuit
LED4 green stays off
Battery
missing
LED
3
lights
Battery fuse blown
LED 3 lights
Battery
low
LED
3
lights
Fault relay has a set of volt free contacts. It deactivates on any fault condition.
Operating ambient temperature range
-5°C to +45°C subject to battery operating range
Relative Humidity
95% Non-condensing (max)