GeneralAire GA50A20 User Manual
Page 5

5
Fig. 5
— Air Cleaner Schematic (with Air Proving Switch)
Electronic Air Cleaner Installation
1. Remove existing equipment filter. Thoroughly clean
fan compartment and ductwork where Air Cleaner is 
to be installed. 
2. Open access door. Slide filters and collecting cells
out of cabinet.
3. Place cabinet in ductwork. Holes are provided to
attach cabinet to ductwork or equipment. If the 
adjoining ductwork is flanged, install the screws so 
that the screw heads are inside the cabinet. This will 
help prevent damage to prefilter and carbon filters 
during removal for cleaning. Never put screws or 
rivets 
into
the
removable
power
box.
When the air duct does not fit the Air Cleaner 
opening, a gradual transition is recommended to 
reduce air turbulence though the air Air Cleaner and 
to increase its efficiency. There should not be more 
than 20º of expansion used on each side of the 
transition fitting. Do not reduce ductwork to a smaller 
Air Cleaner or it will increase the velocity of airflow. 
4. If the Air Cleaner is installed adjacent to an elbow or
angle fitting, turning vanes are recommended to 
improve air distribution across the collecting cells. 
5. After the Air Cleaner has been installed, seal seams
airtight with duct tape or caulking to prevent dust 
from entering the system. 
6. Replace the prefilters in the track on the air entering
side. Place the carbon filters evenly spaced in the 
track on the air exiting side. The collecting cells are 
placed between the tracks, with the arrow on cell 
pointing towards the fan. The cell handle may need 
to be repositioned if the airflow is in a different 
direction than the left to right set up. The handle 
should face the door. Close access door. 
 
Wiring 
Wiring should only be performed by qualified
personnel only. All wiring must comply with all applicable 
codes and standards. The voltage of the power source 
must match the voltage indicated on the Air Cleaner. The 
Air Cleaner must operate ONLY when the system fan is 
running. Make sure the Air Cleaner is properly grounded. 
If the air cleaner is equipped with a cord and plug the
air cleaner can be plugged into an outlet within 6 feet of 
the unit. Do not use an extension cord if the outlet is too 
far away. Have an electrician wire in a new outlet closer 
to the air cleaner. 
If the air cleaner is not equipped with a cord then wire
the Air Cleaner directly to a 120 V power source 
preferably to the same source that is supplying power to 
the furnace or air handler. The APS will power the Air 
Cleaner when there is sufficient airflow to activate the 
sensor. See Fig 5. 
Note: The power switch will be lit even if there is no 
airflow. 
If the unit is to be wired to the EAC contacts on the
system module check that there is sufficient voltage to 
the EAC contacts with the fan operating in all conditions. 
Some systems do not power the contacts on low speed. 
 
SYSTEM CHECK
Perform the following system check before operation. 
1. Replace prefilters, collecting cells and carbon filters. 
Close access door.
2. Turn Air Cleaner power switch ON. Ensure system
fan is operating. Both the power switch light and 
performance indicator light should be lit. The power 
switch light indicates the Air Cleaner has unit voltage. 
The performance indicator light shows that the Air 
Cleaner is operating. 
WARNING
Electrical shock can cause injury or death. Be certain 
main line disconnect switch is off before wiring. 
