GeneralAire DS50 LC Elite Steam User Manual
Page 13

DS 50 / DS 50 LC +030222065 Rev. 1.2
13
Airflow 1000 cfm min.
Airflow
Min 8”
Height >8”
=
=
Airflow
1000 cfm min.
1/3 Height
Airflow
1000 cfm min.
=
=
8” min
24” min
Upstream
36”min
Downstream
IMPORTANT: Allow 1 M ( 3 feet ) of straight duct downstream of the distributor pipes and nozzles for absorption of the steam.
Always allow 0.6M (2 feet) of straight duct upstream of the distributor pipes for evaporation of the steam. Turbulent air flow may
require longer lengths
.
3.4.2
Return Condensate Connection
The return condensate hose from the manifold must be trapped. Coil the hose
into a vertical loop and secure it below the manifold. This water trap prevents
steam from being released into the hose. Insert the barbed fitting into the end
of the hose. Route the manifold drain hose through the top of the humidifier,
into the top of the fill cup. This is just above and to the right of the steam
cylinder. See. Fig. 3.l
Fig. 3.k
Fig. 3.l