Flowline DX10 EchoPod User Manual
Page 4

We do Your Level Best
We do Your Level Best
Step 3: Configure through WebCal
These instructions will walk you through configuration of the EchoPod
®
through
WebCal. For more information, click the WebCal HELP button in the lower right
corner or anywhere on the WebCal screen or refer to the EchoPod
®
manual
found a
Using a Standpipe
A standpipe may be used to dampen turbulence, separate surface foam from the
point of measurement or increase performance in heavy vapor. Select a
3” pipe
(a 2
” pipe is usable, but the minimum) and attach the EchoPod
®
with a coupling
and reducer bushing. The pipe length should run the measurement span and the
bottom of the pipe should remain submerged at all times to prevent foam from
entering the pipe. Cut the bottom end
of the pipe at 45° and drill a 1/4” pressure
equalization hole high in the dead band. The pumps should not drive liquid past the
open end of the standpipe which causes the liquid in the pipe to become turbulent.
WebCal Configuration Screen
Mounting with a Standpipe