beautypg.com

4 operating the appliance, 1 commissioning the boiler, 2 changing the settings – DE DIETRICH DTG 230 User Manual

Page 9: 1 b3 control panel, B3 control panel

background image

9

09/03/2011 - 300011506-001-D

DTG 230

4. Operating the appliance

4 Operating the appliance

4.1 Commissioning the boiler

Initial commissioning must be done by a qualified
professional.

1. Check the water pressure in the installation. Top up with more

water if necessary.

2. Open the gas valve.

3. Make the settings on the control panel:

`

B3 control panel:

- Turn the switch TEST-STB/

.

/

%

to

.

.

- Turn the pump shutdown switch to

9

- Set the boiler thermostat to the desired setting.
- When preparing domestic hot water: Set the DHW thermostat to

the desired setting. Setting 6 (approx 60) recommended.

`

DIEMATIC-m3 control panel:

- Turn the

AUTO /

!

/ TEST STB

switch to AUTO.

- Turn the pump shutdown switch to

9

- Set the boiler thermostat to maximum (between 7½ and 9).

`

K3 control panel (Secondary boiler in cascade with a
DIEMATIC-m3 boiler):

- Set switch AUTO /

!

/ TEST STB to the AUTO position.

4. Turn the burner switch to 2 (2 stage version)

5. Check that the safety thermostat has not triggered. Remove the

safety thermostat hood and press the reset button with a
screwdriver.

6. Set the On/Off switch to 1.

Only for control panel DIEMATIC-m3:
When the boiler is switched on, the tank exchanger is purged
for one minute if a tank is connected and its temperature is
lower than 25°C.
If disgassing has already taken place, press the MODE key to
suspend disgassing.

Only for control panel DIEMATIC-m3:
On commissioning, it is necessary to select the desired
language with the + and - keys and confirm with the MODE key.

4.2 Changing the settings

4.2.1

B3 control panel

Heating temperature setting: Set the boiler thermostat to the
desired setting.
Setting the domestic hot water temperature: Set the DHW
thermostat to the desired setting.