1. Startup and service must be performed
by
a
Factory
Trained
Service
Technician.
2. The unit is for outdoor use only. See
General Information section for more
information.
3. Use only with type of the gas approved
for the boiler. Refer to the boiler rating
plate.
4. Provide adequate combustion ventilation
air to the boiler.
5. Every unit has a unique equipment
nameplate with electrical, operational,
and
unit
clearance
specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
6. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL.
OTHER
IMPORTANT
SAFETY
PRECAUTIONS
ARE
PROVIDED THROUGHOUT THIS
MANUAL.
7. Keep this manual and all literature
safeguarded near or on the unit.
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
WARNING
Always use a pressure regulator,
valves
and
gauges
to
control
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
WARNING
Door
compartments
containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
CAUTION
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used
with
R-410A
and
other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION