Page 22: Electrical

22
Securely fasten the vent pipe joints
according to the following procedure.
1. Insert the male end into the female
section. Push the units together and turn
them until the bead of the male end is
seated against the flared end of the
female
section.
This
creates
the
necessary airtight seal. Align the seams
on the vent lengths and orient them
upward in all horizontal applications.
2. Tighten the locking band with a nut
driver until snug plus 1/4 turn.
Before proceeding, recheck all joints and
ensure that all male sections extend to the
top of the flared female end and all clamps
are tightened.
Figure 9 - Correct Vent Pipe Connection
Stop bead on male end must be pushed
directly against the flared end of the female
end. When checking the inside of the joint,
the gasket is fully covered and out of sight.
Figure 10 - Incorrect Vent Pipe Connection
Boiler Intake Connection
Remove the intake shipping cover. The
round collar on the back of the intake vent
passes through the cabinet wall and slides
over the crimped end of the air intake pipe
inside the unit. This joint should be secured
with aluminum foil tape. The outer flange of
the wall vent is fastened to the outer wall of
the cabinet using sheet metal screws.
Mounting Isolation
For roof mounted applications or anytime
vibration transmission is a factor, vibration
isolators may be used.
Access Doors
Lockable access door is provided to the
electrical and control compartment. A
separate access door is also provided to the
boiler and pumping package compartment.
A light switch is on the wall of the control
compartment.
Electrical
The
single
point
electrical
power
connections are made in the electrical
control compartment.
The microprocessor control furnished with
the unit is supplied with its own power
supply factory wired to the main power of
the outdoor mechanical room.