Warning, Caution – AAON CB-060 User Manual
Page 7
![background image](/manuals/326855/7/background.png)
7
1. Startup and service must be performed
by
a
Factory
Trained
Service
Technician.
2. The unit is for outdoor use only. See
General Information section for more
unit information.
3. Every unit has a unique equipment
nameplate with electrical, operational
and
unit
clearance
specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL.
OTHER
IMPORTANT
SAFETY
PRECAUTIONS
ARE
PROVIDED THROUGHOUT THIS
MANUAL.
5. Keep this manual and all literature
safeguarded near or on the unit.
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
Some
chemical
coil
cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with
the
manufacturer
’s
usage
instructions.
Failure
to
follow
instructions may result in equipment
damage, injury or death.
WARNING
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not
use
alkaline
chemical
coil
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
CAUTION
CAUTION
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNING
Do not work in a closed area where
refrigerant or nitrogen gases may be
leaking. A sufficient quantity of
vapors may be present and cause
injury or death.
WARNING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING