Dimensions, Maintenance – Delta Controls T01 User Manual
Page 3

002522-SENTRY-C : FEB 2012
www.delta-controls.com
DIMENSIONS
Model
Range
DIM A
DIM B
DIM C
P02 / P03
ALL
187
-
-
D01
BC
250
162
89
D02
BD - CE
238
114
77
DC - EA
238
88
77
D03
0D - 0E
263
192
102
DC - EA
263
166
102
T01 / T02
ALL
187
-
-
MAINTENANCE
Inspections should be carried out at quarterly to yearly intervals depending upon operating conditions. Isolate
the unit from process and power and remove the lid. Check all terminals for tightness. Check that cable tails
are not fouled or chafed. Check for internal condensation. Check that the gasket is seated properly in the lid
recess and is not worn. It is recommended that instruments used to provide an alarm are operated periodically
to ensure they are functioning correctly. If further maintenance is required seek advice from DELTA CONTROLS
before attempting repair or replacement of parts.