beautypg.com

Coollogic control system optional features – ClimaCool CoolLogic Control System User Manual

Page 9

background image

9

www.climacoolcorp.com

Chilled Water Temperature Sensor Connections

Chilled water temperature monitoring (entering and leaving)

is a standard feature of the CoolLogic Control System. It is

accomplished by using a factory supplied pair of sensors and

sensor wells which are field installed into ½” weld-o-lets (field

supplied and installed onto the main water headers) within

60” of the entering and leaving chilled water locations.

Condenser Water Temperature Sensor Connections

Condenser water temperature monitoring (entering and

leaving) is a standard feature of the CoolLogic Control System.

It is accomplished by using a factory supplied pair of sensors

and sensor wells which are field installed into ½” weld-o-lets

(field supplied and installed onto the main water headers)

within 60” of the entering and leaving chilled water locations.

Chilled Water Pump and Flow Interlocks

This circuit serves as a proof-of-pump-run circuit and must

exhibit a closed circuit to run. On startup, this circuit will

allow the chiller to run for 10 seconds awaiting a closure

signal feedback, indicating the pump has turned ON. Upon

NO closure signal within 10 seconds, this circuit will shut

the system down. Following a latching alarm, the system

requires a reset and restart to resume operation.

Condenser Water Pump and Flow Interlocks

This circuit serves as a proof-of-pump-run circuit and must

exhibit a closed circuit to run. On startup, this circuit will

allow the chiller to run for 10 seconds awaiting a closure

signal feedback, indicating the pump has turned ON. Upon

NO closure signal within 10 seconds, this circuit will shut

the system down. Following a latching alarm, the system

requires a reset and restart to resume operation.

Building Automation System (BAS) Interface

Internal operational information is available where the

chiller is to be integrated into a building system and

monitored by the equipment of a controls manufacturer.

Available protocols built into the CoolLogic Control System

as standard are:
BACnet over IP , Eternet, MSTP

MODBUS ASCII, RTU

N2

LonWorks

LonWorks® LonTalk Communications Interface

Option

The Master Control Panel provides an optional LonTalk

communication interface between the chiller and the

BAS. Additional hardware is required (Echelon SLTA-10

communications card) to provide “gateway” functionality

between a LonTalk compatible device and the CoolLogic
Control System.

Compressor Unloading

Compressor unloading routines are programmed

into each module controller. When any one of the

module or compressor control parameters approaches a

pre-limit condition, the CoolLogic Control System executes

appropriate compressor unloading commands to avoid

compressor lockout, thus maximizing the chiller system on

time.

Compressor Minimum Off Delay

When a compressor is turned off, the compressor will

remain off for this period of time.

Compressor Minimum On Delay

When a compressor is turned on, the compressor will

remain on for this period of time. This time can be cut short

if an alarm condition is predicted.

CoolLogic Control System Optional Features