Notes for identification:
The transmitter is constructed to be correctly used, according to the conditions set out by the
following table:
Certifications to ATEX 94/9/CE
0722
II 2 G Ex ia IIC T4
0722
II 2 G Ex ia IIC T5
0722
II 2 G Ex ia IIC T6
CESI 09 ATEX 045
Legend of nameplate safety data
Marking of conformity with the applicable European directives
0722
Number of the Notified Body carrying out the surveillance (CESI)
Marking of conformity with Directive 94/9/CE
and relative technical standards
II
Equipment suitable for surface applications (not for mining)
2
Equipment designed to environments in which explosive atmospheres
caused by gases, vapours, mists or mixtures of air and dust may occur, high
level of protection. Suitable for zone 1.
G
Protection for gases, vapours, mists.
Ex ia
Equipment belonging to category "ia" with instrinsic safety.
II C
Suitable for substances (gases) of group IIC,
also suitable for groups IIA and IIB
T4
T5
T6
Temperature class T4 (surface temperature 135°C)
Temperature class T5 (surface temperature 100°C)
Temperature class T6 (surface temperature 85°C)
CESI 09 ATEX 045
Certificate identification:
Name of the laboratory issuing the CE-type-examination certificate
09 = certificate issuing year
045 = certificate number
Ta = 120°C (T4)
Ta = 90°C (T5)
Ta = 75°C (T6)
Ambient temperature –50 to +120 °C
Ambient temperature –50 to +90 °C