Clearance Requirements

• Line voltage and low voltage electrical enclosures must have adequate clearances to meet requirements of NFPA 70

(NEC). This is typically 36" minimum. Note that additional clearance requirements may be required by local codes or
building construction specifications.

• When provided with optional bottom or side casing access plate/panel, provide sufficient clearance to allow access.

• Unit should hang freely, and not make contact with any structure above.

• There are no internally replaceable components in the RF-11 terminal units. All controls are externally accessible.

Electrical Connections

NOTE: This manual was written with the understanding that the line power and control wiring drawings submitted for
the specific project have been acquired and are available during installation.

• Electrical wiring, connections, fusing and installation must conform to the local building codes and the NATIONAL

ELECTRIC CODE (ANSI / NFPA 70).

• Connect the electronically actuated RF-11 per wiring diagram supplied with the unit (or by ATC contractor).

• UL standards dictate that the power source must be within 10% of nameplate voltage, for safety and longevity. If

incoming voltage is 10% above or below nameplate voltage, contact Power Company to correct before operating
terminal.

Start-up Procedures

WARNING: Failure to adhere to these instructions, unauthorized installation, adjustment, alterations, modifications or
maintenance can void the manufacturer’s warranty, cause property damage, personal injury or death. For assistance or
additional information, consult a qualified contractor or an ANEMOSTAT representative.

• Verify all electrical wire terminations are tightened prior to energizing terminal. Some loosening may have occurred

during shipment and installation.

• Prior to start-up, the project specific control sequence / wiring diagram should be read and understood. A copy of

this schematic is located on the interior of the electrical enclosure. If factory supplied analog or DDC controls are
supplied, contact the project control contractor for specific start-up and balancing information.

Maintenance

• The RF-11 VAV terminal unit has been designed and constructed for years of reliable use.

Factory Mounted DDC Controls

Anemostat will factory mount DDC controls of all types. Refer to the wiring diagrams provided by the temperature
control manufacturer for proper wiring of these controls. The maximum and minimum CFM range is determined by the
controls.