CONTROL BOXES

OM--04136

PAGE B -- 7

INSTALLATION

Field Wiring Connections (Incoming Power)

The electrical power used to operate

this pump is high enough to cause inju-

ry or death. Obtain the services of a qu-

alified electrician to make all electrical

connections. Make certain that the

pump and enclosure are properly

grounded; never use gas pipe as an

electrical ground. Be sure that the in-

coming power matches the voltage and

phase of the pump and control before

connecting the power source. Do not

run the pump if the voltage is not within

the limits.

The control is designed to regulate the power sup-

ply. The field wiring must be properly sized to en-
sure an adequate voltage supply. The voltage
available

at the pump motor must be within the in-

dicated range.

Table 1. Pump Motor Voltage Limits

Nominal

Voltage

Minimum

Voltage

Maximum

Voltage

Phase

460

3

420

500

575

3

520

630

230

3

210

250

200

3

180

220

380 (50 Hz)

3

350

420

If the voltage is not within the recommended limits,
obtain the services of a qualified electrician to de-

termine the correct field wiring size and other de-
tails to ensure an adequate voltage supply.

Make certain all connections are tight and that ca-

ble entry points are rainproof. Support the cable
weight, if required, to prevent excessive strain on
cable clamps and cable.

NOTE

After the power cables have been connected to the

control box, make certain the connection is water-

proof.

Power Cable Connections

The electrical power used to operate the

control box is high enough to cause in-

jury or death. Obtain the services of a

qualified electrician to make all electri-

cal connections. Make certain that in-

coming power to the control box is in the

off position and locked out, or that the

power supply to the control box has

been otherwise cut off and locked out,

before connecting power or accessory

cables.

When necessary to change or connect power

cables to the control box, make certain the incom-
ing power is

OFF and LOCKED OUT. Make certain

the control box is

properly grounded and that the

electrical data on the control matches the pump
motor name plate data.

Connect the power cable to the control box as
shown in the wiring diagrams in this section or in-

side the control box door. Use conduit or cable
clamps to secure the power and accessory cables
to the control box. Make certain that all connec-

tions are tight and that cable entry points are
rainproof.

Control Box Adjustments
For control adjustments and settings, refer to the

information inside the control box door.

To maintain overcurrent, short circuit

and ground fault protection, the man-

ufacturer’s instructions for selection of

the heater pack and setting of the in-

stantaneous trip circuit breaker (current

interrupter) or control interface module

must be followed. Failure to follow these

instructions can result in damage to the

pump and/or serious injury to person-

nel.