Troubleshooting - section d – Gorman-Rupp Pumps 82E52-B 1327232 and up User Manual

Page 19

background image

OM−00825

80 SERIES

TROUBLESHOOTING

PAGE D − 1

TROUBLESHOOTING − SECTION D

Review all SAFETY information in Section A.

Before attempting to open or service the
pump:

1. Familiarize yourself with this man-

ual.

2. Lock out or disconnect the power

source to ensure that the pump
will remain inoperative.

3. Allow the pump to completely cool

if overheated.

4. Check the temperature before

opening any covers, plates, or
plugs.

5. Close the suction and discharge

valves.

6. Vent the pump slowly and cau-

tiously.

7. Drain the pump.

TROUBLE

POSSIBLE CAUSE

PROBABLE REMEDY

PUMP FAILS TO
PRIME

Suction check valve contaminated or
damaged.

Clean or replace check valve.

Air leak in suction line.

Lining of suction hose collapsed.

Correct leak.

Replace suction hose.

Leaking or worn seal or pump gasket.

Check pump vacuum. Replace
leaking or worn seal or gasket.

Suction lift or discharge head too high.

Check piping installation and in-
stall bypass line if needed. See
INSTALLATION.

Strainer clogged.

Check strainer and clean if neces-
sary.

Not enough liquid in casing.

Add liquid to casing. See PRIMING.

PUMP STOPS OR
FAILS TO DELIVER
RATED FLOW OR
PRESSURE

Air leak in suction line.

Lining of suction hose collapsed.

Correct leak.

Replace suction hose.

Leaking or worn seal or pump gasket.

Check pump vacuum. Replace
leaking or worn seal or gasket.

Strainer clogged.

Check strainer and clean if neces-
sary.

Suction intake not submerged at
proper level or sump too small.

Check installation and correct sub-
mergence as needed.