Gorman-Rupp Pumps T8A60S-4045H 1514489 and up User Manual
Page 19
OM-06522
SUPER T SERIES
OPERATION
PAGE C - 3
and calibration information.
Typical Messages on the display:
a) EEP bAd... Eeprom memory is not cor
rect, user must recalibrate
unit.
b) USr CAL... User calibrate mode, i.e.,
user wants to calibrate unit.
c) SEt a.oF...
A OFF setpoint, units of lev
el.
d) SEt a.on... A ON setpoint, units of level.
e) SEt b.oF...
B OFF setpoint, units of lev
el.
f) SEt b.on... B ON setpoint, units of level.
g) Hrn dLy...
Horn on, A output delay
time, 5-30 seconds, in
5‐second increments.
h) LO BAT...
Indicator, shows battery
voltage level is below
12VDC.
i) Lo tpt...
Shows status of Low Tem
perature Thermostat con
tacts.
2. LEDs:
a) When the green LED is lighted, the unit is
showing level on the LCD display.
b) When the A output LED is lighted, the A
output relay is closed.
c) When the B output LED is lighted, the B
output relay is closed
NOTE
LED's and all segments of the display are lighted
upon connection of power as a lamp test feature.
However, no relay outputs are closed during test.
3. Switches:
a) The
switch functions as a “round rob
in” type switch. Pressing this switch will
cause the unit to show the next selection
in the order listed above.
b) The
switch functions to decrease the
selection showing. This switch can be
used to decrease the smallest digit by
“bumping” the switch, or to continuously
decrease the digit by pressing and hold
ing for at least one second and releasing
when desired setting is reached.
c. The
switch functions to increase the
selection showing. This switch can be
used to increase the smallest digit by
“bumping” the switch, or to continuously
increase the digit by pressing and hold
ing for at least one second and releasing
when desired setting is reached.
Liquid level adjustment of the Electronic Pressure
Switch is accomplished using the three buttons on
the control. For EPS functions and level adjust
ment, refer to the following instructions.
EPS Functions
Actual functions of the control occur as follows:
Power is applied to the unit.
Unit performs display test for approximately 4
seconds.
When the pressure level showing is equal to or
greater than the “A.on” setpoint, the Horn out
put contacts will close in approximately 1 sec
ond and a delay, equal to the “Hrn dLy” time,
will occur before the A output contacts close.
When the level showing is equal to or greater
than the “B.on” setpoint, the B output contacts
will close in approximately 1 second.
When the pressure decreases to a level equal
to or less than the “B.of” setpoint, B output
contacts will open in approximately one sec
ond.
When the pressure decreases to a level equal
to or less than the “A.of” setpoint, A output con
tacts will open in approximately one second.
If an optional Low Temperature Thermostat is
connected to the unit and the thermostat con
tacts close, the unit displays “lo tpt” on the dis
play. In approximately 1 second, the Horn out
put contacts close, then after the “Hrn dLy”
time, A output contacts close. A output con
tacts will remain closed as long as Low Tem
perature Thermostat contacts are closed.
When the Low Temperature Contacts open, A
output contact will open only if the level is
equal to or less than the “A.off” setpoint.