Global Water

800-876-1172

globalw.com

- 4 -

III. Water Alarm Sensor Installation

a. Water Alarm Sensor specifications.

Output:

Contact Closure (Green and White wires)

Operating Voltage:

10-36VDC

Operating Temperature: -40° to +55°C

Size of Probe:

1" diameter x 5" long

Weight:

1/2 lb.

b. Position the Water Alarm Sensor’s exposed metal pins at the level

where the sensor should alarm.

c. Do not install the WA600 in applications that contain solvents.

Over time, many solvents can deteriorate the cable.

d. The Water Alarm Sensor is a four-wire sensor. Connect the black wire

to ground. The green and white wires form two halves of a circuit.

When water bridges the pins on the end of the sensor it completes the

circuit, acting as a switch. The red wire is positive voltage. Warning:

Always connect the sensor with the power turned off.

IV.

Maintenance

a. The sensor must be cleaned periodically. The suggested cleaning rate

depends on the installation area and how often it contacts the water.

In dirty areas the sensor should be cleaned monthly. In a clean area

they can be cleaned yearly. The sensor can be cleaned using water

and liquid dish soap. A small amount of bleach can be added if there

appears to be algae growth. Metal contact pins should be cleaned

with a bristle brush, soap, and water.