Pump controller 701, Settings – Xylem 701 PUMP CONTROLLER User Manual
Page 3
MJK Automation A/S
Byageren 7
DK-2850 Nærum
Tel:
45 56 06 56
Fax: 45 56 06 46
3
M701GB/0106
PUMP CONTROLLER 701
Pump Controller
Supply
230 V AC
Settings
Pump Controller 701 is operated from the front panel, where
start- and stop levels, or alarm setpoint for each relay output
is adjusted with 2 potentiometers. The pump controller is
adjusted by connection of a voltmeter between the test
bushes, marked "TEST" and "COMMON" and by adjusting
the potentiometer to the desired level. Dependent of the
"LEVEL" switch position, 0 - 3 / 0 - 30 m measuring range is
proportional with 0 - 3 V on the voltmeter and measuring
range
0 - 10 m is equal with 0 - 1 V.
The switch for alternation "ALTERNATION" is set on "ON", if
the pump controller shall be set for alternation.
The voltmeter - (negative) cable is connected to the test bush
"COMMON" and + (positive) is connected to the test bush
"TEST", opposite the function which has to be adjusted.
The pump controller is in operation when connected to
voltage, and calibration can always be made during opera-
tion.