Installation and connection
Pressure transmitter
The pressure transmitter is immersed in
the well. The pressure transmitter can
be mounted in a tube, and fastened at
the top end of the tube, by means of
cable fittings.
If the pressure transmitter is
mounted in a tube, it facilitates
cleaning and inspection.
PUMP CONTROLLER 701
Pressure Transmitter 7060 or 7070
Measuring range: 0 - 3 m:
Pressure Transmitter
7060 / 7070 - 1413
0 - 10 m:Pressure Transmitter
7060 / 7070 - 1423
0 - 30 m:Pressure Transmitter
7060 / 7070 - 1433
Dimension:
Type 7060:
Ø 60 x 140 mm
Type 7070:
Ø 22 x 150 mm
Output:
4 - 20 mA
Supply:
12 - 30 VDC
Accuracy:
±1 % (0 - 50 °C)
Temperature:
- 10 … + 60 °C
Materials:
House 7060: Polypropylene
House 7070: Steel AISI 316
Membrane:
Steel AISI 316
Cable:
Dimension:
2 x 0,5 mm
2
Insulation:
PVC, outer layer of oil
resistant PVC.
Length: 12 m (35 m for 7060 / 7070-1433)
Enclosure:
IP 68, waterproof, max. 3 bar.
Internal diameter
min. 65 mm.