Xylem 4046 ANALOG TO SDI-12 CONVERTER User Manual

Page 4

background image


Change temperature Scale : The default scale is Fahrenheit.


To select the Celsius scale: command aXTC!
sensor response a0011

To select the Fahrenheit scale:

command aXTF!

sensor response a0011

service request a

Results retrieved using a send data command (aD0!)
afahrenheit
or aCelius


Change Sensor Warm-up Time: The analog sensors have a variable warm-up
time. The sensor warm-up time can be 1to 255 seconds. The default time is 4
seconds.


command aXSWttt!
where ttt is the new sensor warm-up time.
sensor response a0011

service request a

The data is retrieved using a Send Data command (aDO!):
Warmup=tttsec


Clear Tipping Bucket Accumulator
This command will “zero” the “precip” count.
command:

aXZP!

sensor response: a0011
service request

a


Results retrieved using a Send Data command (aDO!):

a Tip=0 Offset =(offset value)Slope = (slope value)