2-8 SDI-12 Command and Response Protocol

H-424MS

Example of a H-424MS Extended "Write Wakeup Interval" command:

Command

Response

Time Values

Description

-------------------

------------------------ ------ ---------

-----------------------------

"aXWI20!"

"a0011"

1 sec 1

Write Timer Setting

Command

Response

Description

-------------------

------------------------

----------------------------

"aD0!"

"a+20."

Timer verified at 20.0 seconds

2.9 Write Wake Interval and Write Inactivity Timer Commands

The Wake Interval and Inactivity Timer values control the H-424MS's power save operation. These

values can be written by the SDI-12 host with the following commands. Note only the settings of the

H-424MS which is jumpered for “Master” operation can be accessed.

These commands allows the user to write (change) the timer values. The new value is stored in non-

volatile EEPROM within the H-424MS. Once the new timer value is written to the EEPROM, a

copy is sent to the sensor data buffer for verification. This data can be viewed by using a subsequent

"D" command. To observe the timer settings any other time, use the "Read Wake Interval" or “Read

Inactivity Timer” commands.

Command

Response

Description

-------------

-------------------------

-----------------------------

"aXWWddd!"

"a0011"

Write Wake Interval

"aXWIddd!"

"a0011"

Write Inactivity Timer

Where:

a

is the sensor address ("0-9", "A-Z", "a-z", "*", "?").

XWW

are upper case characters.

XWI

are upper case characters.

ddd

is the new timer value. Valid settings are from 1 to 255 seconds.

The input format is very flexible. Some examples are shown below.

20.0

10

255.0