H-424ms – Xylem H-424MS V1.0 User Manual
Page 23
H-424MS
SDI-12 Command and Response Protocol 2-7
Example of a H-424MS Extended "Read Wake Interval" command:
Command
Response
Time Values
Description
-------------------
------------------------ ------ ---------
-----------------------------
"aXRW!"
"a0011
1 sec 1
Read Value
Command
Response
Description
-------------------
------------------------
-----------------------------
"aD0!"
"a+15.
Wake Interval is 15 seconds
2.8 Read Wake Interval and Read Inactivity Timer Commands
The Wake Interval and Inactivity Timer values control the H-424MS's power save operation. These
values can be read by the SDI-12 host with the following commands. Note only the settings of the
H-424MS which is jumpered for “Master” operation can be read.
The default values are:
Wake Interval:
15 Seconds
Inactivity Timer:
30 Seconds
Command
Response
Description
-------------
-------------------------
-----------------------------
"aXRW!"
"a0011
Read Wake Interval (seconds)
"aXRI!"
"a0011
Read Inactivity Timer (seconds)
Where:
a
is the sensor address ("0-9", "A-Z", "a-z", "*", "?").
XRW
are upper case characters.
XRI
are upper case characters.
This command takes 001 seconds to complete and places 1 value in the data buffer. Use the “aD0"
command to collect and view the value.