LOCAL/REMOTE MODES (Optional Keypad):
In the previous section the soft starter was operated from the keypad (Local Mode). Note the green local
indicator LED on the bottom right of the keypad. For the factory default programming, the selection of the
operation mode (Local/Remote) is made via the “Local/Remote” key (default is Remote). Pressing of the “Local/
Remote” will alternate operation between local & remote. Notice the indicator switches from the green to
the red indicator LED when “Local/Remote” is pressed. If you wish to use an external Local/Remote switch set
P220=4, connect the switch to one of the Digital Inputs (DI1-DI3), and set the corresponding parameter (P263
to 265=2).
To always run in Local mode set P220=0.
To always run in Remote mode set P220=1.
CONTROL AND SIGNAL CONNECTIONS:
Control and signal connections (digital inputs and relay outputs) are made through the terminals (see Figure 3).
Terminal
Description
Specifications
Torque Nm
(in lb)
A1
Electronics Supply
Voltage: 110 to 240 Vac (-15% a +10%)
Current: 140mA Maximum
(factory connections)
0.5 (4.5)
A2
Terminal
Factory Default
Specifications
DI1
Starts/Stops Motor
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15% a +10%)
Current: 2 mA Maximum
DI2
Fault reset
DI3
Fault reset
13
Relay 1 output - Operation
Contact capacity:
Voltage: 250Vac
Current: 1A
14 / 23
Relay common point
24
Relay 2 output - Full voltage
FIGURE 3 – SSW-07 Control and Signal Connections