Section 6

(continued)

For Frame Size 4 Controllers:

Single Phase Connection
For small drives with diode rectifier front end it is possible to run a three phase output with a single phase input.
Only part of the three phase input bridge is used. Ripple current becomes 120 Hz rather than 360. This places a
greater demand on the DC filter components (capacitor bank and DC choke). The result is that the drive must be
derated to 50% current.

The chart below shows the full load output current ratings of the controller when single phase or 3 phase power
is used. If single phase input power is used the Motor Overload switches must be set to 50% or lower.

Supply

Voltage

Frame Size

Model Number

Nominal HP Rating

Controller Full Load

Output Current Rating

3 Phase Input 1 Phase Input 3 Phase Input 1 Phase Input

208/230

1

SPD20050

5.0

2.0

17.8

8.1

SPD20050F

2

SPD20075

7.5

3.0

26.4

10.9

SPD20075F

SPD20100

10.0

5.0

37.0

17.8

SPD20100F

3

SPD20150

15.0

7.5

47.4

26.4

SPD20150F

SPD20200

20.0

10.0

60.6

33.0

SPD20200F

4

SPD20250

25.0

12.0

76.0

40.2

SPD20250F

SPD20300

30.0

15.0

94.0

47.4

SPD20300F

460

1

SPD40050

5.0

8.9

SPD40050F

SPD40075

7.5

13.2

SPD40075F

2

SPD40100

10.0

18.5

SPD40100F

SPD40150

15.0

23.7

SPD40150F

SPD40200

20.0

30.3

SPD40200F

3

SPD40250

25.0

37.5

SPD40250F

SPD40300

30.0

47.0

SPD40300F

POWER SUPPLY AND WIRING