12. On frame-mounted units, tighten foundation, pump

and driver hold-down bolts before connecting piping

to pump.

13. Avoid unnecessary fittings. Select sizes to keep fric-

tion losses low.

14. After completing piping, rotate unit by hand to check

for binding. Note: A screwdriver slot or flats are pro-

vided in end of motor shaft.

3. Alignment

1. No field alignment is necessary on close-coupled

pumps.

2. Even though the pump-motor unit may have a factory

alignment, in transit this alignment could be disturbed

and must be checked prior to running.

3. Check the tightness of all hold-down bolts before

checking the alignment.

4. If re-alignment is necessary, always move the motor.

Shim as required.

5. Final alignment is achieved when parallel and angular

requirements are achieved with both pump and motor

hold down bolts tight.

ALWAYS RECHECK BOTH

ALIGNMENTS AFTER MAKING

ADJUSTMENTS.

6. Parallel misalignment exists when the shafts are not

concentric. Place dial indicator on one hub and rotate

this hub 360º while taking readings on the outside

diameter of the other hub. Parallel alignment occurs

when Total Indicator Reading is .005" or less.

7. Angular misalignment exists when the shafts are not

parallel. Place dial indicator on one hub and rotate this

hub 360º while taking readings on the face of the

other hub. Angular alignment is achieved when Total

Indicator Reading is .005" or less.

4. Suction Piping

1. Low static lift and short, direct suction piping is

desired. For suction lift over 15 feet, consult pump

performance curve for Net Positive Suction Head

Required.

2. Suction pipe size must be at least equal to suction

connection of pump.

3. If larger pipe is used, an eccentric pipe reducer (with

straight side up) must be used at the pump.

4. Installation with pump below source of supply:

4.1. Install isolation valve in piping for inspection and

maintenance.

4.2. Do not use suction isolation valve to throttle

pump!

5. Installation with pump above source of supply:

5.1. To avoid air pockets, no part of piping should be

higher than pump suction connection. Slope

piping upwards from liquid source.

5.2. All joints must be airtight.

5.3. Foot valve to be used only if necessary for prim-

ing, or to hold prime on intermittent service.

5.4. Suction strainer open area must be at least triple

the pipe area.

6. Size of inlet from liquid source, and minimum submer-

gence over inlet, must be sufficient to prevent air

entering pump.

5. Discharge Piping

1. Arrangement must include a check valve located

between a gate valve and the pump. The gate valve is

for regulation of capacity, or inspection of pump or

check valve.

2. If reducer is required, place between check valve and-

pump.

6. Rotation

DO NOT PLACE HANDS IN PUMP

WHILE CHECKING MOTOR

ROTATION. TO DO SO WILL CAUSE

SEVERE PERSONAL INJURY.

1. Pumps are right-hand rotation (Clockwise when

viewed from the driver end). Switch power on and

off. Observe shaft rotation. On frame-mounted units,

check rotation before coupling pump to motor.

2. Single-Phase: Refer to wiring diagram on motor if

rotation must be changed.

3. Three-Phase: Interchange any two power supply leads

to change rotation.

7. Operation

1. Before starting, pump must be primed (free of air and

suction pipe full of liquid) and discharge valve par-

tially open.

PUMPED LIQUID PROVIDES

LUBRICATION. IF PUMP IS RUN

DRY, ROTATING PARTS WILL SEIZE

AND MECHANICAL SEAL WILL BE

DAMAGED.

2. Make complete check after unit is run under operating

conditions and temperature has stabilized. Check for

expansion of piping. Check coupling alignment.

3. Do not operate at or near zero flow. Energy imparted

to the liquid is converted into heat. Liquid may flash

to vapor. Rotating parts require liquid to prevent scor-

ing or seizing.

CAUTION

Hazardous Machinery

WARNING

CAUTION