beautypg.com

Service instructions, Insulation – Bell & Gossett G95873N Circuit Setter Plus Balance Valves With NPT, Flanged and Solder Connections User Manual

Page 3

background image

3

HOW TO USE BELL & GOSSETT CIRCUIT SETTERS
TO PROPORTIONAL BALANCE A SYSTEM

1. Open fully all Circuit Setters on a single pump system.

2. If more than one branch circuit is used, start the balance

procedure by reading all of the flows to the units in a
branch. Each unit (coil) should have its own Circuit Setter
for flow balancing. Using Bell & Gossett RP-250B readout
probes, sequentially attach a Bell & Gossett differential
pressure readout kit to the readout valves on each Circuit
Setter Balance Valve.

3. Using side 2 of the Bell & Gossett Circuit Setter Balance

Valve Calculator, with the top hairline set on zero for the
size Circuit Setter being read, read the flow corresponding
to the pressure drop read with the readout kit.

4. Calculate the ratio of the actual flow to the design flow for

each unit in the branch. This is the proportional flow rate.
(Actual flow divide by design flow.)

5. Select the Circuit Setter with the lowest proportional flow

rate. This Circuit Setter is left in the full open position. Every
other Circuit Setter in the branch is then reset to the same
proportional flow rate.

6. If there are additional branches, repeat the steps in 3, 4 and

5 for each branch.

7. After all branches have been proportionately balanced,

measure the full open flows on the Circuit Setters installed
on the risers. Calculate the proportional ratio of each riser
Circuit Setter and select the one with the lowest proportional
ratio. This Circuit Setter is left fully open and the other riser
Circuit Setters are adjusted to this same ratio as described
in Step “5”.

8. Adjust pump flow so that circuits are receiving their design

flow. This can be accomplished by adjusting a Circuit Setter
Balance Valve installed on the pump discharge or by
changing the pump impeller size.

HOW TO USE BELL & GOSSETT CIRCUIT SETTER
BALANCE VALVES AS FLOW METERS

1. Energize the zone, circuit and/or system pump(s) as

applicable.

2. Using Bell & Gossett Model RP-250B Readout Probes,

sequentially attach a Bell & Gossett differential pressure
readout kit to the readout valves on each Circuit Setter
Balance Valve.

3. Read the differential pressure across the orifice of the

Circuit Setter Balance Valve.

4. Using Side #2 of the Circuit Setter Balance Valve Calculator,

set the hairline over the degree of closure as indicated by
the part of the red plastic knob or indicator plate parallel to
the degree of closure noted on the calibration plate, and
read actual GPM flowing through the Circuit Setter opposite
the gauge reading head loss noted in the white section of
Side #2.

NOTE:

If the system contains a liquid with a specific gravity and/or
viscosity higher or lower than that of water, apply the appropri-
ate correction factor noted in these instructions to obtain the
actual GPM for the system liquid.

WARNING: Hot water leakage can occur from
readout valves during probe insertion and during

hookup of readout kit. Follow the instruction manuals sup-
plied with readout probes and readout kits for safe use.
Failure to follow these instructions could result in serious
personal injury or death and property damage.

IMPORTANT: If a high degree of throttling of flow at pump
discharge is required, Bell & Gossett recommends that the
pump impeller be sized to produce design flow. This will
reduce electrical energy consumption.

WARNING: Hot water leakage can occur from
readout valves during probe insertion and during

hookup of readout kit. Follow the instruction manuals sup-
plied with readout probes and readout kits for safe use.
Failure to follow these instructions could result in serious
personal injury or death and property damage.

HOW  TO  USE  BELL  &  GOSSETT  CIRCUIT  SETTER

BALANCE VALVES AS AN ISOLATION VALVE

1. Move the adjustment knob or stem until the position indica-

tor aligns with the closed position on the calibration plate.

2. Close the isolation valve on the other side of the equipment

to be serviced.

3. Open  the  drain  valve  to  drain  the  system  between  the

Circuit Setter and second isolation valve.

HOW TO USE THE MEMORY STOP FEATURE

For sizes 

1

/

2

" thru 4":

1. Make the final degree of closure setting.
2. Loosen  the  memory  stop  locking  screw  in  the  slot  on  the

top of the red knob.

3. Slide the memory stop screw in the slot (counter-clockwise

for 

1

/

2

"  thru  1"  sizes  and  clockwise  for  1

1

/

4

"  thru  4"  sizes)

until the screw stops.

4. Tighten the memory stop screw.

SERVICE INSTRUCTIONS

Periodically  inspect  the  Circuit  Setter  for  signs  of  leakage  or

corrosion.

WARNING: Check for proper sealing when using as 

an  isolation  valve.  If  the  seat  is  not  sealing  properly

liquid  will  continue  to  flow  from  the  drain  valves.  In  this

case  the  Circuit  Setter  must  be  isolated  from  the  system

and  replaced.  Failure  to  follow  these  instructions  could

result  in  serious  personal  injury  or  death  and  property 

damage.

WARNING: Corrosion or leakage are indications that

the  Circuit  Setter  must  be  replaced.  Failure  to 

follow  these  instructions  could  result  in  serious  personal

injury or death and property damage.

INSULATION

Bell & Gossett recommends that insulation be attached to the

Circuit  Setter  after  the  system  has  been  balanced  and  the

completed G95872 tag has been wired to the Circuit Setter.
NOTE:

Tape or other acceptable means should be used to secure the

insulation to the Circuit Setter Balance Valve.

B&G CIRCUIT SETTER 

CORRECTION FACTORS FOR 

VISCOSITY AND SPECIFIC GRAVITY

GPMƒ =

Ø

GPM

s

S.G.

GPMƒ = ƒ GPM

s

ƒ =

Ø

S.G.

GPMƒ – FLUID FLOW
GPM

s

– FLOW THRU SETTER

(a MEASURED CONDITIONS)

Ø – VISCOSITY CORRECTION
S.G. – SPECIFIC GRAVITY (TO WATER)