Table a, Figure 2, Note: 5- wire systems – Comfort Stat CP1818 User Manual
Page 2: Ndo not connect a “common” wire (sometimes, Troubleshoo, Ting
system.
y The number of wires in your system can be as few as two (for heat only
inal marking on the existing thermostat of two wire,
PLY THE
ling wires, disconnect them from the existing thermostat.
wall
res, seal this hole with
If the code letter on
then
e wire
and connect to
th
l
OTE:
ount wallplate and Thermostat
systems), as many as eight, or any number in between. If you follow the
labeling procedures correctly, you do not have to be concerned about how
many wires there are.
y There is often no term
heat only systems. Just connect either of the wires to the RH terminal, then
connect the other wire to the W terminal to complete the circuit.
y IMPORTANT! BEFORE DISCONNECTING ANY WIRES, AP
SELFADHESIVE LABELS PROVIDED TO THE WIRE AS SHOWN IN
TABLE A BELOW. (For example, attach the label marked W to the wire that
toes to the W or H terminal on your existing thermostat.) IGNORE THE
COLOR OF THE WIRES since these do not always comply with the
standard.
y After labe
y Remove existing wallplate. To make sure wires do not fall back into
opening, you may want to tape them to the wall.
y If hole in wall is larger than necessary for wi
insulating material so that no hot or cold air can enter the back of the
thermostat from the wall. This air could cause a false thermostat reading.
Table A
your existing
Thermostat is
mark th
with label shown
ermostat termina
shown
N
Do not connect a “Common” wire (sometimes
labeled “C”) to any terminal on this thermostat. Tape up the wire and do not
use. This wire provides electricity to non-battery powered thermostats.
M
at by pressing the release tab
y Position wallplate on wall and
g wires through large opening.
y
ntil flush
y
wallplate to wall, pulling wires through large opening. Insert
e 3
NOTE: 5- Wire Systems
If your thermostat has one wire marked R or Rh (2, 3, or 4-wire system),
ire between the Rh and Rc terminals on the
y Remove the wallplate from your thermost
on the bottom of the thermostat. See Figure 2.
Figure 2
pull existin
Then level for appearance. Mark holes for plastic anchors provided, if
your existing holes do not line up with those on the wallplate.
Drill holes with 3/16” bit and gently tap anchors into the holes u
with wall.
Reposition
mounting screws provided into wall anchor and tighten. See Figure 3.
Figur
then leave the jumper w
wallplate. Otherwise, if you have separate Rh and Rc wires (5-wire system),
then remove the jumper wire between the Rh and Rc terminals.
Connect Wires and Mount Thermostat to wallplate
y Match and connect the labeled wires to the appropriate coded terminal
ich may
efer to the Wiring Diagrams below to be sure your system is wired
rrectly.
the System Selector switch inside the thermostat to the Heat
stem or thermostat.
. Press the bottom of the thermostat body into the snap on the
screws on the wallplate. (See Figure 4, 5.) Ignore any wires wh
be present, but which were note connected to the old thermostat.
Figure 4 Figure 5
y R
co
y If your system is a single stage heat pump and uses an O or B wire, you
must move
Pump position. If you have a normal furnace or electric system, leave the
switch in the Standard position. Refer to the System Selector section on the
back for more information on this switch.
y Be sure to tighten the terminal screws securely, otherwise a loose wire
could cause operational problems with your sy
y Push excess wire back into the hole to prevent interference when
installing the thermostat to the wallplate.
y Make sure the System Switch is set to OFF, and the Fan Switch is set to
AUTO.
yInsert the tabs on top of the thermostat body into the slots at the top of the
wallplate
bottom of the wallplate. Refer to Figure 2. (NOTE: Do not force the
thermostat onto the wallplate, as the terminal pins may be damaged. If it
does not snap properly, the thermostat may not work.)
y Insert the two AA size alkaline batteries, observing the polarity marked
inside the battery compartment.
y Switch on the main power at the panel or furnace.
Wiring Diagrams
X-No Connection
Selector Switches
tor switches on the printed circuit board inside the
“HG” position. Leave it in this
rner. If you have an electric
fan relay.
sition. Leave it in this
tric, or hot water
rmostat is set for F˚ mode from the factory. In order to change to C˚
key about 2 seconds without the
Figure 6
TROUBLESHOO
In order for this thermostat to control your system, the system type must be
specified by the selec
thermostat. There is also a selector switch for your choice of Fahrenheit or
Celsius temperature display. See figure 6.
y Heating System Selector (HG – HE switch)
The factory position for this switch is in the
position if you have a gas furnace or an oil bu
furnace, test to see whether the Heat and Fan come on as expected after
installation. If the Fan operation is normal, leave it in the “HG” position. If
the Fan does not come on within a minute of the thermostat calling for
heating, change the switch position to “HE”. The system selector has no
effect in the cooling mode.
NOTE: “HG” position is for gas and most other systems. “HE” position is for
certain electric systems having a
y System Selector (STANDARD – HEAT PUMP switch)
The factory position for this switch is in the STD po
position if you have ANY system that uses gas, oil, elec
heating. If you have a single-stage Heat Pump (no auxiliary or emergency
heat source), then slide the switch to the HP position. Be sure the reversing
valve wire is connected to the correct terminal for your heat pump (Rc/O) or
(Rh/B).
y F˚ / C˚ selector (Fahrenheit / Celsius)
Your the
mode, slide the switch to C˚ and hold any
battery, then place the battery again.
NOTE: Unless press any key about 2 seconds without the battery, then
place the battery again.
TING
Problem Solution
1. Check battery connections and batteries.
No Display
2. Move the battery out and wait for about 1
minutes then Replace Batteries..
Entire Display
Dims.
1. Replace Batteries.
Auto Fan Does Not
Turn On Properly.
or to correct position.
1. Move HG/HE select
1. Check that the function switch is in the correct
position (“HEAT” or “COOL”).
2. There may be as much as 4-mintue delay
before the system turns On – wait and check.
(Compressor protection delay.)
3.
Check your circuit breakers and switches to
ensure there is power to the system.
4. Replace batteries.
5. Ma
closed
ke sure your furnace blower door is
properly.
6. If your non-heat pump system only uses
4-wires, be sure the jumper wire is installed
between the Rh/B and Rc/O terminals.
7
.
. Check the position of the Reversing Valve
selector switch: Standard or Heat Pump
Heating or Cooling
Does Not Go On or
nd
Off.
8. If you have single-stage heat pump, be sure
the jumper wire is installed between the Y a
W terminals.
Erratic Display
1.
n. Then reprogram.
Move the battery out hold any key then place
the battery agai
If unit continues to
operate in the Off
position.
1. Replace unit.
Thermostat
permanently reads
or
1. Replace unit.
“HI”, “LO”,
“E1” , “E2”.
If
her problems, call us for technical assistance.
T
number is 1-866-591-9898
you experience any ot
he service
1 2 3 4
STD
HP
HG
HE
K3
JP2
F
C
K5
L
N
R G W Y
Rh
AC24V
N
L
120V
AC
120V
AC
120V
AC
120V
AC
120V
AC
120V
AC
N
L
AC24V
N
L
AC24V
N
L
AC24V
N
L
AC24V
N
L
AC24V
N
L
AC24V
W
R
L
Rh/O
G
Y
R
c/B
N